Skip to content
Fencer Vulns
high 7.5

CVE-2018-13798 json

A vulnerability has been identified in SICAM A8000 CP-8000 (All versions < V14), SICAM A8000 CP-802X (All versions < V14), SICAM A8000 CP-8…

published 2019-03-21 7 y ago modified 2026-06-17 4 mo ago also EUVD-2018-5734

cvss
7.5
version 3.0, NVD
cisa kev
Not listed
not in CISA's catalog
epss
2.0%
EPSS 2.0% chance of exploitation in 30 days, percentile 80%
public exploits
0
none known

Summary

A vulnerability has been identified in SICAM A8000 CP-8000 (All versions < V14), SICAM A8000 CP-802X (All versions < V14), SICAM A8000 CP-8050 (All versions < V2.00). Specially crafted network packets sent to port 80/TCP or 443/TCP could allow an unauthenticated remote attacker to cause a Denial-of-Service condition of the web server. The security vulnerability could be exploited by an attacker with network access to the affected systems on port 80/TCP or 443/TCP. Successful exploitation requires no system privileges and no user interaction. An attacker could use the vulnerability to compromise availability of the web server. A system reboot is required to recover the web service of the device. At the time of advisory update, exploit code for this security vulnerability is public.

Patch / fix

  • siemens sicam_a8000_cp-8000_firmware 14
  • siemens sicam_a8000_cp-802x_firmware 14
  • siemens sicam_a8000_cp-8050_firmware 2.00

Vendor advisories

What the vendors themselves say about their products: affected, fixed or not affected, and what to do.

cisa ICSA-19-038-01 updated cvss 5.3

ICSA-19-038-01 Siemens SICAM A8000 RTU Series

Facts from CISA's republication of the vendor's own advisory (CSAF); the linked advisory is the authoritative source. CISA notification · csaf

Exploit prediction

1.99% chance of exploitation in the next 30 days, higher than 80% of all scored CVEs (FIRST EPSS, 2026-11-08).

CVSS scores

assigned by version score vector
NVD 3.0 7.5 CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
NVD 2.0 7.8 AV:N/AC:L/Au:N/C:N/I:N/A:C

Affected products

  • Siemens AG SICAM A8000 CP-8000, SICAM A8000 CP-802X, SICAM A8000 CP-8050
  • Siemens AG SICAM A8000 CP-802X
  • Siemens AG SICAM A8000 CP-8050

Classification

Weakness
  • CWE-20 Improper Input Validation

References

Sources