CVE-2018-4840 json
A vulnerability has been identified in DIGSI 4 (All versions < V4.92), EN100 Ethernet module DNP3 variant (All versions < V1.05.00), EN100…
published 2018-03-08 8 y ago modified 2026-06-17 4 mo ago also EUVD-2018-16626
- cvss
- 7.5
- version 3.0, NVD
- cisa kev
- Not listed
- not in CISA's catalog
- epss
- 1.8%
- EPSS 1.8% chance of exploitation in 30 days, percentile 78%
- public exploits
- 0
- none known
Summary
A vulnerability has been identified in DIGSI 4 (All versions < V4.92), EN100 Ethernet module DNP3 variant (All versions < V1.05.00), EN100 Ethernet module IEC 104 variant (All versions), EN100 Ethernet module IEC 61850 variant (All versions < V4.30), EN100 Ethernet module Modbus TCP variant (All versions), EN100 Ethernet module PROFINET IO variant (All versions). The device engineering mechanism allows an unauthenticated remote user to upload a modified device configuration overwriting access authorization passwords.
Patch / fix
- siemens siprotec_compact_7sj80_firmware 4.77
- siemens siprotec_compact_7sk80_firmware 4.77
- siemens siprotec_4_7sj66_firmware 4.30
- siemens digsi_4 4.92
- siemens en100_ethernet_module_iec_61850_firmware 4.30
Vendor advisories
What the vendors themselves say about their products: affected, fixed or not affected, and what to do.
cisa ICSA-18-067-01 updated cvss 7.5
Siemens SIPROTEC 4, SIPROTEC Compact, DIGSI 4, and EN100 Ethernet Module (Update D)
-
Siemens DIGSI 4 <V4.92affected: fixed in V4.92, mitigation support.industry.siemens.com
-
Siemens EN100 Ethernet module DNP3 variant <V1.05.00affected: fixed in V1.05.00, mitigation support.industry.siemens.com
-
Siemens EN100 Ethernet module IEC 104 variantaffected: mitigation, no fix available
-
Siemens EN100 Ethernet module IEC 61850 variant <V4.30affected: fixed in V4.30, mitigation support.industry.siemens.com
-
Siemens EN100 Ethernet module Modbus TCP variant Siemens EN100 Ethernet module PROFINET IO variantaffected: mitigation, no fix available
Facts from CISA's republication of the vendor's own advisory (CSAF); the linked advisory is the authoritative source. CISA notification · csaf
Exploit prediction
1.78% chance of exploitation in the next 30 days, higher than 78% of all scored CVEs (FIRST EPSS, 2026-11-08).
CVSS scores
| assigned by | version | score | vector |
|---|---|---|---|
| NVD | 3.0 | 7.5 | CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N |
| NVD | 2.0 | 5.0 | AV:N/AC:L/Au:N/C:N/I:P/A:N |
Affected products
- Siemens DIGSI 4
- Siemens EN100 Ethernet module DNP3 variant
- Siemens EN100 Ethernet module IEC 104 variant
- Siemens EN100 Ethernet module IEC 61850 variant
- Siemens EN100 Ethernet module Modbus TCP variant
- Siemens EN100 Ethernet module PROFINET IO variant
Classification
- Weakness
-
- CWE-306 Missing Authentication for Critical Functionality
References
-
cert-portal.siemens.com
/productcert/pdf/ssa-203306.pdf
patch, vendor-advisory
-
ics-cert.us-cert.gov
/advisories/ICSA-18-067-01
third-party-advisory, us-government-resource
Sources
- CVE List CVE-2018-4840
- NVD CVE-2018-4840
Fencer Vulns keeps one entry per vulnerability: the CVE id wins, then GHSA, and records that alias each other are merged, except that two CVEs always keep separate entries. The same data is available as JSON.