CVE-2018-7790 json
An Information Management Error vulnerability exists in Schneider Electric's Modicon M221 product (all references, all versions prior to fi…
published 2018-08-29 8 y ago modified 2026-06-17 4 mo ago also EUVD-2018-19502
- cvss
- 9.8
- version 3.1, CNA
- cisa kev
- Not listed
- not in CISA's catalog
- epss
- 2.4%
- EPSS 2.4% chance of exploitation in 30 days, percentile 84%
- public exploits
- 0
- none known
Summary
An Information Management Error vulnerability exists in Schneider Electric's Modicon M221 product (all references, all versions prior to firmware V1.6.2.0). The vulnerability allows unauthorized users to replay authentication sequences. If an attacker exploits this vulnerability and connects to a Modicon M221, the attacker can upload the original program from the PLC.
Patch / fix
- schneider-electric modicon_m221_firmware 1.6.2.0
Vendor advisories
What the vendors themselves say about their products: affected, fixed or not affected, and what to do.
cisa ICSA-18-240-01 updated cvss 7.1
Schneider Electric Modicon M221
-
Schneider Electric Software, LLC Modicon M221 all references < 1.6.2.0affected: mitigation “As a temporary mitigation, Modicon M221 users should take the following measures: Set up a firewall blocking all remote/external access to Port 502.” schneider-electric.com
From CISA ICS and IT advisories (CSAF, https://github.com/cisagov/CSAF), a U.S. Government work; changed: reduced to products, statuses and remediations. CISA notification · csaf
CISA SSVC
- Exploitation
- none
- Automatable
- yes
- Technical impact
- total
- Assessed
- 5 mo ago
Exploit prediction
2.38% chance of exploitation in the next 30 days, higher than 84% of all scored CVEs (FIRST EPSS, 2026-11-08).
CVSS scores
| assigned by | version | score | vector |
|---|---|---|---|
| CISA ADP | 3.1 | 9.8 | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H |
| NVD | 3.1 | 9.8 | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H |
| CNA | 3.1 | 9.8 | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H |
| NVD | 2.0 | 7.5 | AV:N/AC:L/Au:N/C:P/I:P/A:P |
Affected products
- Schneider Electric SE Modicon M221, all references, all versions prior to firmware V1.6.2.0
Classification
- Weakness
-
- CWE-294 Authentication Bypass by Capture-replay
References
-
schneider-electric.com
/en/download/document/SEVD-2018-235-01/
mitigation, vendor-advisory
-
securityfocus.com
/bid/105182
vdb-entry, third-party-advisory
Sources
- CVE List CVE-2018-7790
- NVD CVE-2018-7790
Fencer Vulns keeps one entry per vulnerability: the CVE id wins, then GHSA, and records that alias each other are merged, except that two CVEs always keep separate entries. The same data is available as JSON.