Summary

A remote code execution security issue exists within Studio 5000 Logix Designer® due to incorrect authorization on a configuration file. This can allow any authenticated user to modify the paths of external tools configured within the application. If exploited, an attacker could alter the configuration to point to a malicious executable, resulting in arbitrary code execution when any user interacts with the external tools functionality.

Patch / fix

  • rockwellautomation studio_5000_logix_designer 33.02, 34.02

Vendor advisories

What the vendors themselves say about their products: affected, fixed or not affected, and what to do.

cisa ICSA-26-202-10 updated cvss 7.5

Rockwell Automation Studio 5000 Logix Designer

  • Rockwell Automation Studio 5000 Logix Designer V35.00, >=V32.00, <=V32.04, V34.00, V34.01
    affected: vendor fix, mitigation “For more information, see Rockwell Automation Security Advisories: https://www.rockwellautomation.com/en-us/trust-center/security-advisories.html.” support.rockwellautomation.com

From CISA ICS and IT advisories (CSAF, https://github.com/cisagov/CSAF), a U.S. Government work; changed: reduced to products, statuses and remediations. CISA notification · csaf

CISA SSVC

Exploitation
none
Automatable
no
Technical impact
total
Assessed
3 mo ago

Exploit prediction

0.15% chance of exploitation in the next 30 days, higher than 4% of all scored CVEs (FIRST EPSS, 2026-11-08).

CVSS scores

assigned by version score vector
CNA 4.0 7.3 CVSS:4.0/AV:L/AC:H/AT:P/PR:L/UI:A/VC:H/VI:H/VA:H/SC:H/SI:H/SA:H
CNA 4.0 7.3 CVSS:4.0/AV:L/AC:H/AT:P/PR:L/UI:A/VC:H/VI:H/VA:H/SC:H/SI:H/SA:H/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X
NVD 3.1 7.5 CVSS:3.1/AV:L/AC:H/PR:L/UI:R/S:C/C:H/I:H/A:H