CVE-2026-9108 json
Studio 5000 Logix Designer® – Multiple Vulnerabilities
published 2026-07-14 3 mo ago modified 2026-10-24 15 d ago also EUVD-2026-43707
- cvss
- 7.5
- version 3.1, NVD
- cisa kev
- Not listed
- not in CISA's catalog
- epss
- 0.2%
- EPSS 0.2% chance of exploitation in 30 days, percentile 7%
- public exploits
- 0
- none known
Summary
A path traversal security issue exists within Studio 5000 Logix Designer® due to improper limitation of file paths within ACD project files. The software does not sanitize or validate file names embedded in the ACD file structure during the project opening procedure, allowing path traversal sequences to escape the intended extraction directory. If exploited, an attacker could craft a malicious ACD project file that results in arbitrary files being written to attacker-controlled locations on the file system, potentially leading to code execution.
Patch / fix
- rockwellautomation studio_5000_logix_designer 32.05, 33.04, 34.04, 35.02
Vendor advisories
What the vendors themselves say about their products: affected, fixed or not affected, and what to do.
cisa ICSA-26-202-10 updated cvss 6.7
Rockwell Automation Studio 5000 Logix Designer
-
Rockwell Automation Studio 5000 Logix Designer V36.00, V35.00, V35.01, >=V34.00, <=V34.03affected: vendor fix, mitigation “For more information, see Rockwell Automation Security Advisories: https://www.rockwellautomation.com/en-us/trust-center/security-advisories.html.” support.rockwellautomation.com
From CISA ICS and IT advisories (CSAF, https://github.com/cisagov/CSAF), a U.S. Government work; changed: reduced to products, statuses and remediations. CISA notification · csaf
CISA SSVC
- Exploitation
- none
- Automatable
- no
- Technical impact
- total
- Assessed
- 3 mo ago
Exploit prediction
0.18% chance of exploitation in the next 30 days, higher than 7% of all scored CVEs (FIRST EPSS, 2026-11-08).
CVSS scores
| assigned by | version | score | vector |
|---|---|---|---|
| CNA | 4.0 | 5.4 | CVSS:4.0/AV:L/AC:H/AT:P/PR:L/UI:A/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N |
| CNA | 4.0 | 5.4 | CVSS:4.0/AV:L/AC:H/AT:P/PR:L/UI:A/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X |
| NVD | 3.1 | 7.5 | CVSS:3.1/AV:L/AC:H/PR:L/UI:R/S:C/C:H/I:H/A:H |
Affected products
- Rockwell Automation Studio 5000 Logix Designer
Classification
- Weakness
-
- CWE-22 Improper Limitation of a Pathname to a Restricted Directory
References
Sources
- CVE List CVE-2026-9108
- NVD CVE-2026-9108
Fencer Vulns keeps one entry per vulnerability: the CVE id wins, then GHSA, and records that alias each other are merged, except that two CVEs always keep separate entries. The same data is available as JSON.