Skip to content
Fencer Vulns
medium 6.3

CVE-2026-2491 json

Socomec DIRIS A-40 HTTP API Authentication Bypass Vulnerability

published 2026-03-13 7 mo ago modified 2026-06-17 4 mo ago also EUVD-2026-12107

cvss
6.3
version 3.0, CNA
cisa kev
Not listed
not in CISA's catalog
epss
0.5%
EPSS 0.5% chance of exploitation in 30 days, percentile 44%
public exploits
0
none known

Summary

Socomec DIRIS A-40 HTTP API Authentication Bypass Vulnerability. This vulnerability allows network-adjacent attackers to bypass authentication on affected installations of Socomec DIRIS A-40 power monitoring devices. Authentication is not required to exploit this vulnerability.

The specific flaw exists within the web API implementation, which listens on TCP port 80 by default. The issue results from the lack of authentication prior to allowing access to functionality. An attacker can leverage this vulnerability to bypass authentication on the system. Was ZDI-CAN-23993.

CISA SSVC

Exploitation
none
Automatable
no
Technical impact
partial
Assessed
7 mo ago

Exploit prediction

0.52% chance of exploitation in the next 30 days, higher than 44% of all scored CVEs (FIRST EPSS, 2026-11-08).

CVSS scores

assigned by version score vector
CNA 3.0 6.3 CVSS:3.0/AV:A/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:L

Affected products

  • Socomec DIRIS A-40

Classification

Weakness
  • CWE-306 Missing Authentication for Critical Functionality

References

Sources

Fencer Vulns keeps one entry per vulnerability: the CVE id wins, then GHSA, and records that alias each other are merged, except that two CVEs always keep separate entries. The same data is available as JSON.