CVE-2025-57882 json
AutomationDirect CLICK PLUS Improper Resource Shutdown or Release
published 2025-09-23 13 mo ago modified 2026-10-18 21 d ago also EUVD-2025-30933
- cvss
- 5.9
- version 3.1, CNA
- cisa kev
- Not listed
- not in CISA's catalog
- epss
- 0.3%
- EPSS 0.3% chance of exploitation in 30 days, percentile 26%
- public exploits
- 0
- none known
Summary
An improper resource shutdown or release vulnerability has been identified in the Click Plus C2-03CPU-2 device running firmware version 3.60. The vulnerability allows an unauthenticated attacker to perform a denial-of-service attack by exhausting all available device sessions in the Remote PLC application.
Patch / fix
- AutomationDirect CLICK PLUS C0-0x CPU firmware v3.71
- AutomationDirect CLICK PLUS C0-1x CPU firmware v3.71
- AutomationDirect CLICK PLUS C2-x CPU firmware v3.71
Vendor advisories
What the vendors themselves say about their products: affected, fixed or not affected, and what to do.
cisa ICSA-25-266-01 updated cvss 5.9
AutomationDirect CLICK PLUS
-
AutomationDirect CLICK PLUS C0-0x CPU firmware <v3.71 AutomationDirect CLICK PLUS C0-1x CPU firmware <v3.71 AutomationDirect CLICK PLUS C2-x CPU firmware <v3.71affected: mitigation “AutomationDirect recommends that users update CLICK PLUS and firmware to V3.80.” automationdirect.com
From CISA ICS and IT advisories (CSAF, https://github.com/cisagov/CSAF), a U.S. Government work; changed: reduced to products, statuses and remediations. CISA notification · csaf
CISA SSVC
- Exploitation
- none
- Automatable
- no
- Technical impact
- partial
- Assessed
- 13 mo ago
Exploit prediction
0.33% chance of exploitation in the next 30 days, higher than 26% of all scored CVEs (FIRST EPSS, 2026-11-08).
CVSS scores
| assigned by | version | score | vector |
|---|---|---|---|
| CNA | 4.0 | 8.2 | CVSS:4.0/AV:N/AC:H/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N |
| CNA | 3.1 | 5.9 | CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H |
| CNA | 4.0 | 8.2 | CVSS:4.0/AV:N/AC:H/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X |
Affected products
- AutomationDirect CLICK PLUS C0-0x CPU firmware
- AutomationDirect CLICK PLUS C0-1x CPU firmware
- AutomationDirect CLICK PLUS C2-x CPU firmware
Classification
- Weakness
-
- CWE-404 Improper Resource Shutdown or Release
References
Sources
- CVE List CVE-2025-57882
- NVD CVE-2025-57882
Fencer Vulns keeps one entry per vulnerability: the CVE id wins, then GHSA, and records that alias each other are merged, except that two CVEs always keep separate entries. The same data is available as JSON.