CVE-2025-40556 json
A vulnerability has been identified in BACnet ATEC 550-440 (All versions), BACnet ATEC 550-441 (All versions), BACnet ATEC 550-445 (All ver…
published 2025-05-13 17 mo ago modified 2026-06-17 4 mo ago also EUVD-2025-14681
- cvss
- 6.5
- version 3.1, CNA
- cisa kev
- Not listed
- not in CISA's catalog
- epss
- 0.3%
- EPSS 0.3% chance of exploitation in 30 days, percentile 16%
- public exploits
- 0
- none known
Summary
A vulnerability has been identified in BACnet ATEC 550-440 (All versions), BACnet ATEC 550-441 (All versions), BACnet ATEC 550-445 (All versions), BACnet ATEC 550-446 (All versions). Affected devices improperly handle specific incoming BACnet MSTP messages. This could allow an attacker residing in the same BACnet network to send a specially crafted MSTP message that results in a denial of service condition of the targeted device. A power cycle is required to restore the device's normal operation.
Vendor advisories
What the vendors themselves say about their products: affected, fixed or not affected, and what to do.
cisa ICSA-25-135-03 updated cvss 6.5
Siemens BACnet ATEC Devices
-
Siemens BACnet ATEC 550-440 Siemens BACnet ATEC 550-441 Siemens BACnet ATEC 550-445 Siemens BACnet ATEC 550-446affected: no fix planned
Facts from CISA's republication of the vendor's own advisory (CSAF); the linked advisory is the authoritative source. CISA notification · csaf
CISA SSVC
- Exploitation
- none
- Automatable
- no
- Technical impact
- partial
- Assessed
- 17 mo ago
Exploit prediction
0.25% chance of exploitation in the next 30 days, higher than 16% of all scored CVEs (FIRST EPSS, 2026-11-08).
CVSS scores
| assigned by | version | score | vector |
|---|---|---|---|
| CNA | 3.1 | 6.5 | CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H |
| CNA | 4.0 | 7.1 | CVSS:4.0/AV:A/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N |
| CNA | 4.0 | 7.1 | CVSS:4.0/AV:A/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X |
Affected products
- Siemens BACnet ATEC 550-440
- Siemens BACnet ATEC 550-441
- Siemens BACnet ATEC 550-445
- Siemens BACnet ATEC 550-446
Classification
- Weakness
-
- CWE-20 Improper Input Validation