CVE-2025-13824 json
Micro820®, Micro850®, Micro870® – Specialized Fuzzing Vulnerabilities
published 2025-12-15 10 mo ago modified 2026-10-07 32 d ago also EUVD-2025-203385
- cvss
- 8.7
- version 4.0, CNA
- cisa kev
- Not listed
- not in CISA's catalog
- epss
- 0.3%
- EPSS 0.3% chance of exploitation in 30 days, percentile 28%
- public exploits
- 0
- none known
Summary
A security issue exists due to improper handling of malformed CIP packets during fuzzing. The controller enters a hard fault with solid red Fault LED and becomes unresponsive. Upon power cycle, the controller will enter recoverable fault where the MS LED and Fault LED become flashing red and reports fault code 0xF019. To recover, clear the fault.
Vendor advisories
What the vendors themselves say about their products: affected, fixed or not affected, and what to do.
cisa ICSA-25-352-07 updated cvss 7.5
Rockwell Automation Micro820, Micro850, Micro870
-
Rockwell Automation Micro820 <=V14.011affected: vendor fix, mitigation “Rockwell Automation recommends users of Micro850/870 update to V12.013 or later. The update can be downloaded from the Rockwell Automation website.” compatibility.rockwellautomation.com
From CISA ICS and IT advisories (CSAF, https://github.com/cisagov/CSAF), a U.S. Government work; changed: reduced to products, statuses and remediations. CISA notification · csaf
CISA SSVC
- Exploitation
- none
- Automatable
- yes
- Technical impact
- partial
- Assessed
- 10 mo ago
Exploit prediction
0.34% chance of exploitation in the next 30 days, higher than 28% of all scored CVEs (FIRST EPSS, 2026-11-08).
CVSS scores
| assigned by | version | score | vector |
|---|---|---|---|
| CNA | 4.0 | 8.7 | CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N |
| CNA | 4.0 | 8.7 | CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X |
Affected products
- Rockwell Automation Micro820®, Micro850®, Micro870®
Classification
- Weakness
-
- CWE-763 Release of Invalid Pointer or Reference