CVE-2025-0694 json
CODESYS Control V3 removable media path traversal
published 2025-03-18 19 mo ago modified 2026-06-17 4 mo ago also EUVD-2025-7368
- cvss
- 6.6
- version 3.1, CNA
- cisa kev
- Not listed
- not in CISA's catalog
- epss
- 0.3%
- EPSS 0.3% chance of exploitation in 30 days, percentile 20%
- public exploits
- 0
- none known
Summary
Insufficient path validation in CODESYS Control allows low privileged attackers with physical access to gain full filesystem access.
Patch / fix
- CODESYS CODESYS Control for BeagleBone SL 4.16.0.0
- CODESYS CODESYS Control for emPC-A/iMX6 SL 4.16.0.0
- CODESYS CODESYS Control for IOT2000 SL 4.16.0.0
- CODESYS CODESYS Control for Linux ARM SL 4.16.0.0
- CODESYS CODESYS Control for Linux SL 4.16.0.0
- CODESYS CODESYS Control for PFC100 SL 4.16.0.0
- CODESYS CODESYS Control for PFC200 SL 4.16.0.0
- CODESYS CODESYS Control for PLCnext SL 4.16.0.0
- CODESYS CODESYS Control for Raspberry Pi SL 4.16.0.0
- CODESYS CODESYS Control for WAGO Touch Panels 600 SL 4.16.0.0
- CODESYS CODESYS Control RTE (for Beckhoff CX) SL 3.5.21.0
- CODESYS CODESYS Control RTE (SL) 3.5.21.0
- CODESYS CODESYS Control Win (SL) 3.5.21.0
- CODESYS CODESYS Runtime Toolkit 3.5.21.0
- CODESYS CODESYS Virtual Control SL 4.16.0.0
Vendor advisories
What the vendors themselves say about their products: affected, fixed or not affected, and what to do.
cisa ICSA-26-076-01 updated cvss 6.6
CODESYS in Festo Automation Suite
-
CODESYS Development System 3.0 Festo Automation Suite 2.8.0.137, Festo Automation Suite < 2.8.0.138 CODESYS Development System 3.5.16.10 Festo Automation Suite 2.8.0.137, Festo Automation Suite < 2.8.0.138affected: mitigation
-
Festo Automation Suite 2.8.0.138 CODESYS Development System 3.5.21.20fixed
Facts from CISA's republication of the vendor's own advisory (CSAF); the linked advisory is the authoritative source. CISA notification · csaf
CISA SSVC
- Exploitation
- none
- Automatable
- no
- Technical impact
- total
- Assessed
- 19 mo ago
Exploit prediction
0.28% chance of exploitation in the next 30 days, higher than 20% of all scored CVEs (FIRST EPSS, 2026-11-08).
CVSS scores
| assigned by | version | score | vector |
|---|---|---|---|
| CNA | 3.1 | 6.6 | CVSS:3.1/AV:P/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H |
Affected products
- CODESYS CODESYS Control for BeagleBone SL
- CODESYS CODESYS Control for emPC-A/iMX6 SL
- CODESYS CODESYS Control for IOT2000 SL
- CODESYS CODESYS Control for Linux ARM SL
- CODESYS CODESYS Control for Linux SL
- CODESYS CODESYS Control for PFC100 SL
- CODESYS CODESYS Control for PFC200 SL
- CODESYS CODESYS Control for PLCnext SL
- CODESYS CODESYS Control for Raspberry Pi SL
- CODESYS CODESYS Control for WAGO Touch Panels 600 SL
- CODESYS CODESYS Control RTE (for Beckhoff CX) SL
- CODESYS CODESYS Control RTE (SL)
- CODESYS CODESYS Control Win (SL)
- CODESYS CODESYS Runtime Toolkit
- CODESYS CODESYS Virtual Control SL
Classification
- Weakness
-
- CWE-22 Improper Limitation of a Pathname to a Restricted Directory
References
Sources
- CVE List CVE-2025-0694
- NVD CVE-2025-0694