CVE-2024-47902 json
A vulnerability has been identified in InterMesh 7177 Hybrid 2.0 Subscriber (All versions < V8.2.12), InterMesh 7707 Fire Subscriber (All v…
published 2024-10-23 2 y ago modified 2026-06-17 4 mo ago also EUVD-2024-42717
- cvss
- 7.2
- version 3.1, CNA
- cisa kev
- Not listed
- not in CISA's catalog
- epss
- 0.5%
- EPSS 0.5% chance of exploitation in 30 days, percentile 43%
- public exploits
- 0
- none known
Summary
A vulnerability has been identified in InterMesh 7177 Hybrid 2.0 Subscriber (All versions < V8.2.12), InterMesh 7707 Fire Subscriber (All versions < V7.2.12 only if the IP interface is enabled (which is not the default configuration)). The web server of affected devices does not authenticate GET requests that execute specific commands (such as `ping`) on operating system level.
Patch / fix
- Siemens InterMesh 7177 Hybrid 2.0 Subscriber V8.2.12
- Siemens InterMesh 7707 Fire Subscriber V7.2.12
- siemens intermesh_7177_hybrid2.0_subscriber 8.2.12
- siemens intermesh_7707_fire_subscriber 7.2.12
Vendor advisories
What the vendors themselves say about their products: affected, fixed or not affected, and what to do.
cisa ICSA-24-303-01 updated cvss 7.2
Siemens InterMesh Subscriber Devices
-
Siemens InterMesh 7177 Hybrid 2.0 Subscriber <V8.2.12affected: fixed in V8.2.12, workaround
-
Siemens InterMesh 7707 Fire Subscriber <V7.2.12affected: fixed in V7.2.12, workaround, mitigation
Facts from CISA's republication of the vendor's own advisory (CSAF); the linked advisory is the authoritative source. CISA notification · csaf
CISA SSVC
- Exploitation
- none
- Automatable
- no
- Technical impact
- total
- Assessed
- 2 y ago
Exploit prediction
0.51% chance of exploitation in the next 30 days, higher than 43% of all scored CVEs (FIRST EPSS, 2026-11-08).
CVSS scores
| assigned by | version | score | vector |
|---|---|---|---|
| CNA | 3.1 | 7.2 | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:L/I:L/A:N |
| CNA | 4.0 | 6.9 | CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:L/VI:L/VA:N/SC:L/SI:L/SA:N |
| CNA | 4.0 | 6.9 | CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:L/VI:L/VA:N/SC:L/SI:L/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X |
| NVD | 3.1 | 9.8 | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H |
Affected products
- Siemens InterMesh 7177 Hybrid 2.0 Subscriber
- Siemens InterMesh 7707 Fire Subscriber
- siemens intermesh_7177_hybrid2.0_subscriber
- siemens intermesh_7707_fire_subscriber
Classification
- Weakness
-
- CWE-306 Missing Authentication for Critical Functionality
References
-
cert-portal.siemens.com
/productcert/html/ssa-333468.html
vendor-advisory
Sources
- CVE List CVE-2024-47902
- NVD CVE-2024-47902
Fencer Vulns keeps one entry per vulnerability: the CVE id wins, then GHSA, and records that alias each other are merged, except that two CVEs always keep separate entries. The same data is available as JSON.