CVE-2024-42512 json
Security Update for the OPC UA .NET Standard Stack
published 2025-02-10 20 mo ago modified 2026-10-15 25 d ago also GHSA-h958-fxgg-g7w3 , EUVD-2025-5035
- cvss
- 8.6
- version 3.1, CNA
- cisa kev
- Not listed
- not in CISA's catalog
- epss
- 0.6%
- EPSS 0.6% chance of exploitation in 30 days, percentile 48%
- public exploits
- 0
- none known
Summary
Vulnerability in the OPC UA .NET Standard Stack before 1.5.374.158 allows an unauthorized attacker to bypass application authentication when the deprecated Basic128Rsa15 security policy is enabled.
Patch / fix
- nuget OPCFoundation.NetStandard.Opc.Ua.Core 1.5.374.158
- Siemens SIMATIC Energy Manager PRO V7.4 V7.4 Update 7
- Siemens SIMATIC Energy Manager PRO V7.5 V7.5 Update 2
- Siemens SIMIT V11 V11.3
Vendor advisories
What the vendors themselves say about their products: affected, fixed or not affected, and what to do.
cisa ICSA-25-072-09 updated cvss 7.4
Siemens OPC UA
-
Siemens SIMATIC Energy Manager PRO V7.2 Siemens SIMATIC Energy Manager PRO V7.3affected: no fix planned
-
Siemens SIMATIC Energy Manager PRO V7.4 >=V7.4Update0, <V7.4Update7affected: fixed in V7.4 support.industry.siemens.com
-
Siemens SIMATIC Energy Manager PRO V7.5 >=V7.5Update0, <V7.5Update2affected: fixed in V7.5 support.industry.siemens.com
-
Siemens SIMIT V11 < 11.3affected: fixed in V11.3 support.industry.siemens.com
Facts from CISA's republication of the vendor's own advisory (CSAF); the linked advisory is the authoritative source. CISA notification · csaf
CISA SSVC
- Exploitation
- none
- Automatable
- yes
- Technical impact
- partial
- Assessed
- 20 mo ago
Exploit prediction
0.59% chance of exploitation in the next 30 days, higher than 48% of all scored CVEs (FIRST EPSS, 2026-11-08).
CVSS scores
| assigned by | version | score | vector |
|---|---|---|---|
| CISA ADP | 3.1 | 8.6 | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:L/A:L |
| CNA | 3.1 | 8.6 | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:L/A:L |
| GitHub | 3.1 | 5.9 | CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:N/A:N |
Affected packages
| ecosystem | package | affected | fixed in |
|---|---|---|---|
| nuget | OPCFoundation.NetStandard.Opc.Ua.Core | <1.5.374.158 |
1.5.374.158 |
Affected products
- Siemens SIMATIC Energy Manager PRO V7.2
- Siemens SIMATIC Energy Manager PRO V7.3
- Siemens SIMATIC Energy Manager PRO V7.4
- Siemens SIMATIC Energy Manager PRO V7.5
- Siemens SIMIT V11
Classification
References
-
github.com
/OPCFoundation/UA-.NETStandard/commit/3543d0292556691f681e39145e2de4526b90487d
web
-
files.opcfoundation.org
/SecurityBulletins/OPC%20Foundation%20Security%20Bulletin%20CVE-2024-42512.pdf
web, vendor-advisory
- cert-portal.siemens.com /productcert/html/ssa-858251.html
-
github.com
/OPCFoundation/UA-.NETStandard/security/advisories/GHSA-h958-fxgg-g7w3
web
-
nvd.nist.gov
/vuln/detail/CVE-2024-42512
advisory
-
github.com
/OPCFoundation/UA-.NETStandard
package
Sources
- CVE List CVE-2024-42512
- GitHub Advisory GHSA-h958-fxgg-g7w3
- NVD CVE-2024-42512
Fencer Vulns keeps one entry per vulnerability: the CVE id wins, then GHSA, and records that alias each other are merged, except that two CVEs always keep separate entries. The same data is available as JSON.