CVE-2022-46670 json
Rockwell Automation MicroLogix 1100 & 1400 Vulnerable to Cross-Site Scripting Attack
published 2022-12-16 3 y ago modified 2026-06-17 4 mo ago also EUVD-2022-49466
- cvss
- 7.1
- version 3.1, CNA
- cisa kev
- Not listed
- not in CISA's catalog
- epss
- 0.6%
- EPSS 0.6% chance of exploitation in 30 days, percentile 48%
- public exploits
- 0
- none known
Summary
Rockwell Automation was made aware of a vulnerability by a security researcher from Georgia Institute of Technology that the MicroLogix 1100 and 1400 controllers contain a vulnerability that may give an attacker the ability to accomplish remote code execution. The vulnerability is an unauthenticated stored cross-site scripting vulnerability in the embedded webserver. The payload is transferred to the controller over SNMP and is rendered on the homepage of the embedded website.
Vendor advisories
What the vendors themselves say about their products: affected, fixed or not affected, and what to do.
cisa ICSA-22-354-04 updated cvss 7.1
Rockwell Automation MicroLogix 1100 and 1400
-
Rockwell Automation MicroLogix 1100 Rockwell Automation MicroLogix 1400 A <= 7.000 Rockwell Automation MicroLogix 1400 B/C <= 21.007affected: mitigation “Disable the web server, if possible (This component is an optional feature and disabling it will not disrupt the intended use of the device)” rockwellautomation.custhelp.com
From CISA ICS and IT advisories (CSAF, https://github.com/cisagov/CSAF), a U.S. Government work; changed: reduced to products, statuses and remediations. CISA notification · csaf
CISA SSVC
- Exploitation
- none
- Automatable
- no
- Technical impact
- partial
- Assessed
- 18 mo ago
Exploit prediction
0.58% chance of exploitation in the next 30 days, higher than 48% of all scored CVEs (FIRST EPSS, 2026-11-08).
CVSS scores
| assigned by | version | score | vector |
|---|---|---|---|
| CNA | 3.1 | 7.1 | CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:C/C:L/I:L/A:L |
| NVD | 3.1 | 6.1 | CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:C/C:L/I:L/A:N |
Affected products
- Rockwell Automation MicroLogix 1100 & 1400 Controllers
- Rockwell Automation MicroLogix 1400-B/C
- Rockwell Automation MicroLogix 1400-A
Classification
- Weakness
-
- CWE-79 Improper Neutralization of Input During Web Page Generation
References
Sources
- CVE List CVE-2022-46670
- NVD CVE-2022-46670
Fencer Vulns keeps one entry per vulnerability: the CVE id wins, then GHSA, and records that alias each other are merged, except that two CVEs always keep separate entries. The same data is available as JSON.