CVE-2022-43398 json
A vulnerability has been identified in POWER METER SICAM Q100 (All versions < V2.50), POWER METER SICAM Q100 (All versions < V2.50), POWER…
published 2022-11-08 4 y ago modified 2026-06-17 4 mo ago also EUVD-2022-46436
- cvss
- 7.5
- version 3.1, CNA
- cisa kev
- Not listed
- not in CISA's catalog
- epss
- 0.6%
- EPSS 0.6% chance of exploitation in 30 days, percentile 48%
- public exploits
- 0
- none known
Summary
A vulnerability has been identified in POWER METER SICAM Q100 (All versions < V2.50), POWER METER SICAM Q100 (All versions < V2.50), POWER METER SICAM Q100 (All versions < V2.50), POWER METER SICAM Q100 (All versions < V2.50). Affected devices do not renew the session cookie after login/logout and also accept user defined session cookies. An attacker could overwrite the stored session cookie of a user. After the victim logged in, the attacker is given access to the user's account through the activated session.
Patch / fix
- siemens 7kg9501-0aa01-2aa1_firmware 2.50
- siemens 7kg9501-0aa31-2aa1_firmware 2.50
Vendor advisories
What the vendors themselves say about their products: affected, fixed or not affected, and what to do.
cisa ICSA-23-166-03 updated cvss 7.5
Siemens SICAM Q200 Devices
-
Siemens POWER METER SICAM Q200 family <V2.70affected: fixed in V2.70, mitigation support.industry.siemens.com
Facts from CISA's republication of the vendor's own advisory (CSAF); the linked advisory is the authoritative source. CISA notification · csaf
cisa ICSA-22-314-11 updated cvss 7.5
Siemens SICAM Q100
-
Siemens POWER METER SICAM Q100 (7KG9501-0AA01-0AA1) <V2.50 Siemens POWER METER SICAM Q100 (7KG9501-0AA01-2AA1) <V2.50 Siemens POWER METER SICAM Q100 (7KG9501-0AA31-0AA1) <V2.50 Siemens POWER METER SICAM Q100 (7KG9501-0AA31-2AA1) <V2.50affected: fixed in V2.50, workaround
Facts from CISA's republication of the vendor's own advisory (CSAF); the linked advisory is the authoritative source. CISA notification · csaf
Exploit prediction
0.60% chance of exploitation in the next 30 days, higher than 48% of all scored CVEs (FIRST EPSS, 2026-11-08).
CVSS scores
| assigned by | version | score | vector |
|---|---|---|---|
| CNA | 3.1 | 7.5 | CVSS:3.1/AV:N/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:H/E:P/RL:O/RC:C |
| CNA | 3.1 | 7.5 | CVSS:3.1/AV:N/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:H |
| NVD | 3.1 | 8.8 | CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H |
Affected products
- Siemens POWER METER SICAM Q100
Classification
- Weakness
-
- CWE-384 Session Fixation
References
-
cert-portal.siemens.com
/productcert/pdf/ssa-570294.pdf
mitigation, patch, vendor-advisory
- cert-portal.siemens.com /productcert/pdf/ssa-887249.pdf
Sources
- CVE List CVE-2022-43398
- NVD CVE-2022-43398
Fencer Vulns keeps one entry per vulnerability: the CVE id wins, then GHSA, and records that alias each other are merged, except that two CVEs always keep separate entries. The same data is available as JSON.