CVE-2022-30315 json
Honeywell Experion PKS Safety Manager (SM and FSC) through 2022-05-06 has Insufficient Verification of Data Authenticity.
published 2022-07-28 4 y ago modified 2026-06-17 4 mo ago also EUVD-2022-52264
- cvss
- 9.8
- version 3.1, NVD
- cisa kev
- Not listed
- not in CISA's catalog
- epss
- 1.0%
- EPSS 1.0% chance of exploitation in 30 days, percentile 62%
- public exploits
- 0
- none known
Summary
Honeywell Experion PKS Safety Manager (SM and FSC) through 2022-05-06 has Insufficient Verification of Data Authenticity. According to FSCT-2022-0053, there is a Honeywell Experion PKS Safety Manager insufficient logic security controls issue. The affected components are characterized as: Honeywell FSC runtime (FSC-CPU, QPP), Honeywell Safety Builder. The potential impact is: Remote Code Execution, Denial of Service. The Honeywell Experion PKS Safety Manager family of safety controllers utilize the unauthenticated Safety Builder protocol (FSCT-2022-0051) for engineering purposes, including downloading projects and control logic to the controller. Control logic is downloaded to the controller on a block-by-block basis. The logic that is downloaded consists of FLD code compiled to native machine code for the CPU module (which applies to both the Safety Manager and FSC families). Since this logic does not seem to be cryptographically authenticated, it allows an attacker capable of triggering a logic download to execute arbitrary machine code on the controller's CPU module in the context of the runtime. While the researchers could not verify this in detail, the researchers believe that the microprocessor underpinning the FSC and Safety Manager CPU modules is incapable of offering memory protection or privilege separation capabilities which would give an attacker full control of the CPU module. There is no authentication on control logic downloaded to the controller. Memory protection and privilege separation capabilities for the runtime are possibly lacking. The researchers confirmed the issues in question on Safety Manager R145.1 and R152.2 but suspect the issue affects all FSC and SM controllers and associated Safety Builder versions regardless of software or firmware revision. An attacker who can communicate with a Safety Manager controller via the Safety Builder protocol can execute arbitrary code without restrictions on the CPU module, allowing for covert manipulation of control operations and implanting capabilities similar to the TRITON malware (MITRE ATT&CK software ID S1009). A mitigating factor with regards to some, but not all, of the above functionality is that these require the Safety Manager physical keyswitch to be in the right position.
Vendor advisories
What the vendors themselves say about their products: affected, fixed or not affected, and what to do.
cisa ICSA-22-207-02 updated cvss 7.5
Honeywell Safety Manager
-
Honeywell Safety Manageraffected: vendor fix, mitigation “Honeywell has identified the following specific workarounds and mitigations users can apply to reduce risk:” process.honeywell.com
From CISA ICS and IT advisories (CSAF, https://github.com/cisagov/CSAF), a U.S. Government work; changed: reduced to products, statuses and remediations. CISA notification · csaf
Exploit prediction
0.99% chance of exploitation in the next 30 days, higher than 62% of all scored CVEs (FIRST EPSS, 2026-11-08).
CVSS scores
| assigned by | version | score | vector |
|---|---|---|---|
| NVD | 3.1 | 9.8 | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H |
Classification
- Weakness
-
- CWE-345 Insufficient Verification of Data Authenticity
References
-
forescout.com
/blog/
third-party-advisory
-
cisa.gov
/uscert/ics/advisories/icsa-22-207-02
mitigation, third-party-advisory, us-government-resource
Sources
- CVE List CVE-2022-30315
- NVD CVE-2022-30315