Skip to content
Fencer Vulns
medium 6.1

CVE-2022-23127 json

Cross-site Scripting vulnerability in Mitsubishi Electric MC Works64 versions 4.04E (10.95.210.01) and prior and ICONICS MobileHMI versions…

published 2022-01-21 4 y ago modified 2026-06-17 4 mo ago also EUVD-2022-28218

cvss
6.1
version 3.1, NVD
cisa kev
Not listed
not in CISA's catalog
epss
1.6%
EPSS 1.6% chance of exploitation in 30 days, percentile 76%
public exploits
0
none known

Summary

Cross-site Scripting vulnerability in Mitsubishi Electric MC Works64 versions 4.04E (10.95.210.01) and prior and ICONICS MobileHMI versions 10.96.2 and prior allows a remote unauthenticated attacker to gain authentication information of an MC Works64 or MobileHMI and perform any operation using the acquired authentication information, by injecting a malicious script in the URL of a monitoring screen delivered from the MC Works64 server or MobileHMI server to an application for mobile devices and leading a legitimate user to access this URL.

Patch / fix

  • mitsubishielectric mc_works64 10.95.210.01

Exploit prediction

1.61% chance of exploitation in the next 30 days, higher than 76% of all scored CVEs (FIRST EPSS, 2026-11-08).

CVSS scores

assigned by version score vector
NVD 3.1 6.1 CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:C/C:L/I:L/A:N
NVD 2.0 4.3 AV:N/AC:M/Au:N/C:N/I:P/A:N

Affected products

  • n/a Mitsubishi Electric MC Works64; ICONICS MobileHMI

Classification

Weakness
  • CWE-79 Improper Neutralization of Input During Web Page Generation