CVE-2021-45033 json
A vulnerability has been identified in CP-8000 MASTER MODULE WITH I/O -25/+70°C (All versions < V16.20), CP-8000 MASTER MODULE WITH I/O -40…
published 2022-01-11 4 y ago modified 2026-06-17 4 mo ago also EUVD-2021-31830
- cvss
- 8.8
- version 3.1, NVD
- cisa kev
- Not listed
- not in CISA's catalog
- epss
- 0.9%
- EPSS 0.9% chance of exploitation in 30 days, percentile 61%
- public exploits
- 0
- none known
Summary
A vulnerability has been identified in CP-8000 MASTER MODULE WITH I/O -25/+70°C (All versions < V16.20), CP-8000 MASTER MODULE WITH I/O -40/+70°C (All versions < V16.20), CP-8021 MASTER MODULE (All versions < V16.20), CP-8022 MASTER MODULE WITH GPRS (All versions < V16.20). An undocumented debug port uses hard-coded default credentials. If this port is enabled by a privileged user, an attacker aware of the credentials could access an administrative debug shell on the affected device.
Patch / fix
- siemens cp-8000_master_module_with_i/o_-25/+70_firmware 16.20
- siemens cp-8000_master_module_with_i/o_-40/+70_firmware 16.20
- siemens cp-8021_master_module_firmware 16.20
- siemens cp-8022_master_module_with_gprs_firmware 16.20
Vendor advisories
What the vendors themselves say about their products: affected, fixed or not affected, and what to do.
cisa ICSA-22-013-02 updated cvss 9.9
Siemens SICAM A8000
-
Siemens CP-8000 MASTER MODULE WITH I/O -25/+70°C <V16.20 Siemens CP-8000 MASTER MODULE WITH I/O -40/+70°C <V16.20 Siemens CP-8021 MASTER MODULE <V16.20 Siemens CP-8022 MASTER MODULE WITH GPRS <V16.20affected: fixed in V16.20 support.industry.siemens.com
Facts from CISA's republication of the vendor's own advisory (CSAF); the linked advisory is the authoritative source. CISA notification · csaf
Exploit prediction
0.94% chance of exploitation in the next 30 days, higher than 61% of all scored CVEs (FIRST EPSS, 2026-11-08).
CVSS scores
| assigned by | version | score | vector |
|---|---|---|---|
| NVD | 3.1 | 8.8 | CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H |
| NVD | 2.0 | 8.5 | AV:N/AC:M/Au:S/C:C/I:C/A:C |
Affected products
- Siemens CP-8000 MASTER MODULE WITH I/O -25/+70°C
- Siemens CP-8000 MASTER MODULE WITH I/O -40/+70°C
- Siemens CP-8021 MASTER MODULE
- Siemens CP-8022 MASTER MODULE WITH GPRS
Classification
- Weakness
-
- CWE-798 Use of Hard-coded Credentials
References
-
cert-portal.siemens.com
/productcert/pdf/ssa-324998.pdf
patch, vendor-advisory
Sources
- CVE List CVE-2021-45033
- NVD CVE-2021-45033
Fencer Vulns keeps one entry per vulnerability: the CVE id wins, then GHSA, and records that alias each other are merged, except that two CVEs always keep separate entries. The same data is available as JSON.