CVE-2021-37172 json
A vulnerability has been identified in SIMATIC S7-1200 CPU family (incl.
published 2021-08-10 5 y ago modified 2026-06-17 4 mo ago also EUVD-2021-23746
- cvss
- 7.5
- version 3.1, NVD
- cisa kev
- Not listed
- not in CISA's catalog
- epss
- 0.9%
- EPSS 0.9% chance of exploitation in 30 days, percentile 60%
- public exploits
- 0
- none known
Summary
A vulnerability has been identified in SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (V4.5.0). Affected devices fail to authenticate against configured passwords when provisioned using TIA Portal V13. This could allow an attacker using TIA Portal V13 or later versions to bypass authentication and download arbitrary programs to the PLC. The vulnerability does not occur when TIA Portal V13 SP1 or any later version was used to provision the device.
Patch / fix
Vendor advisories
What the vendors themselves say about their products: affected, fixed or not affected, and what to do.
cisa ICSA-21-222-09 updated cvss 8.1
Siemens SIMATIC S7-1200 (Update A)
-
Siemens SIMATIC S7-1200 CPU family (incl. SIPLUS variants) V4.5.0affected: fixed in V4.5.1, mitigation support.industry.siemens.com
Facts from CISA's republication of the vendor's own advisory (CSAF); the linked advisory is the authoritative source. CISA notification · csaf
Exploit prediction
0.92% chance of exploitation in the next 30 days, higher than 60% of all scored CVEs (FIRST EPSS, 2026-11-08).
CVSS scores
| assigned by | version | score | vector |
|---|---|---|---|
| NVD | 3.1 | 7.5 | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N |
| NVD | 2.0 | 5.0 | AV:N/AC:L/Au:N/C:N/I:P/A:N |
Affected products
- Siemens SIMATIC S7-1200 CPU family (incl. SIPLUS variants)
Classification
- Weakness
-
- CWE-287 Improper Authentication
References
-
cert-portal.siemens.com
/productcert/pdf/ssa-830194.pdf
patch, vendor-advisory
Sources
- CVE List CVE-2021-37172
- NVD CVE-2021-37172
Fencer Vulns keeps one entry per vulnerability: the CVE id wins, then GHSA, and records that alias each other are merged, except that two CVEs always keep separate entries. The same data is available as JSON.