CVE-2021-22792 json
A CWE-476: NULL Pointer Dereference vulnerability that could cause a Denial of Service on the Modicon PLC controller / simulator when updat…
published 2021-09-02 5 y ago modified 2026-06-17 4 mo ago also EUVD-2021-9927
- cvss
- 6.5
- version 3.1, CNA
- cisa kev
- Not listed
- not in CISA's catalog
- epss
- 1.0%
- EPSS 1.0% chance of exploitation in 30 days, percentile 61%
- public exploits
- 0
- none known
Summary
A CWE-476: NULL Pointer Dereference vulnerability that could cause a Denial of Service on the Modicon PLC controller / simulator when updating the controller application with a specially crafted project file exists in Modicon M580 CPU (part numbers BMEP* and BMEH*, all versions), Modicon M340 CPU (part numbers BMXP34*, all versions), Modicon MC80 (part numbers BMKC80*, all versions), Modicon Momentum Ethernet CPU (part numbers 171CBU*, all versions), PLC Simulator for EcoStruxureª Control Expert, including all Unity Pro versions (former name of EcoStruxureª Control Expert, all versions), PLC Simulator for EcoStruxureª Process Expert including all HDCS versions (former name of EcoStruxureª Process Expert, all versions), Modicon Quantum CPU (part numbers 140CPU*, all versions), Modicon Premium CPU (part numbers TSXP5*, all versions).
Patch / fix
CISA SSVC
- Exploitation
- none
- Automatable
- no
- Technical impact
- partial
- Assessed
- 5 mo ago
Exploit prediction
0.95% chance of exploitation in the next 30 days, higher than 61% of all scored CVEs (FIRST EPSS, 2026-11-08).
CVSS scores
| assigned by | version | score | vector |
|---|---|---|---|
| CISA ADP | 3.1 | 6.5 | CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H |
| NVD | 3.1 | 7.5 | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H |
| CNA | 3.1 | 6.5 | CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H |
| NVD | 2.0 | 5.0 | AV:N/AC:L/Au:N/C:N/I:N/A:P |
Affected products
- n/a Modicon M580 CPU (part numbers BMEP* and BMEH*, all versions), Modicon M340 CPU (part numbers BMXP34*, all versions), Modicon MC80 (part numbers BMKC80*, all versions), Modicon Momentum Ethernet CPU (part numbers 171CBU*, all versions), PLC Simulator for EcoStruxureª Control Expert, including all Unity Pro versions (former name of EcoStruxureª Control Expert, all versions), PLC Simulator for EcoStruxureª Process Expert including all HDCS versions (former name of EcoStruxureª Process Expert, all versions), Modicon Quantum CPU (part numbers 140CPU*, all versions), Modicon Premium CPU (part numbers TSXP5*, all versions)
Classification
- Weakness
-
- CWE-476 NULL Pointer Dereference
References
-
download.schneider-electric.com
/files?p_Doc_Ref=SEVD-2021-222-04
patch, vendor-advisory
-
download.schneider-electric.com
/files?p_Doc_Ref=SEVD-2021-222-07
not-applicable
Sources
- CVE List CVE-2021-22792
- NVD CVE-2021-22792
Fencer Vulns keeps one entry per vulnerability: the CVE id wins, then GHSA, and records that alias each other are merged, except that two CVEs always keep separate entries. The same data is available as JSON.