CVE-2020-6998 json
Rockwell Automation CompactLogix 5370 and ControlLogix 5570 Controllers Improper Input Validation
published 2022-07-27 4 y ago modified 2026-06-17 4 mo ago also EUVD-2020-28138
- cvss
- 5.8
- version 3.1, CNA
- cisa kev
- Not listed
- not in CISA's catalog
- epss
- 3.2%
- EPSS 3.2% chance of exploitation in 30 days, percentile 88%
- public exploits
- 0
- none known
Summary
The connection establishment algorithm found in Rockwell Automation CompactLogix 5370 and ControlLogix 5570 versions 33 and prior does not sufficiently manage its control flow during execution, creating an infinite loop. This may allow an attacker to send specially crafted CIP packet requests to a controller, which may cause denial-of-service conditions in communications with other products.
Vendor advisories
What the vendors themselves say about their products: affected, fixed or not affected, and what to do.
cisa ICSA-21-061-02 updated cvss 5.8
Rockwell Automation CompactLogix 5370 and ControlLogix 5570 Controllers (Update A)
-
Rockwell Automation Armor Compact GuardLogix 5370 controllers <= 33 Rockwell Automation Armor GuardLogix Safety Controllers <= 33 Rockwell Automation Compact GuardLogix 5370 controllers <= 33 Rockwell Automation CompactLogix 5370 L1 controllers <= 33 Rockwell Automation CompactLogix 5370 L2 controllers <= 33 Rockwell Automation CompactLogix 5370 L3 controllers <= 33affected: mitigation “Rockwell Automation recommends affected users apply firmware v33.011 or later.” compatibility.rockwellautomation.com
+1 more productsfewer
Rockwell Automation ControlLogix 5570 controllers <= 33
From CISA ICS and IT advisories (CSAF, https://github.com/cisagov/CSAF), a U.S. Government work; changed: reduced to products, statuses and remediations. CISA notification · csaf
CISA SSVC
- Exploitation
- none
- Automatable
- yes
- Technical impact
- partial
- Assessed
- 18 mo ago
Exploit prediction
3.16% chance of exploitation in the next 30 days, higher than 88% of all scored CVEs (FIRST EPSS, 2026-11-08).
CVSS scores
| assigned by | version | score | vector |
|---|---|---|---|
| CNA | 3.1 | 5.8 | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:L |
| NVD | 3.1 | 8.6 | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H |
Affected products
- Rockwell Automation Armor Compact GuardLogix 5370 controllers
- Rockwell Automation Armor GuardLogix Safety Controllers
- Rockwell Automation CompactLogix 5370 L1 controllers
- Rockwell Automation CompactLogix 5370 L2 controllers
- Rockwell Automation CompactLogix 5370 L3 controllers
- Rockwell Automation Compact GuardLogix 5370 controllers
- Rockwell Automation ControlLogix 5570 controllers
Classification
- Weakness
-
- CWE-20 Improper Input Validation
References
-
rockwellautomation.custhelp.com
/app/answers/answer_view/a_id/1130398
permissions-required, vendor-advisory
-
cisa.gov
/uscert/ics/advisories/icsa-21-061-02
third-party-advisory, us-government-resource
Sources
- CVE List CVE-2020-6998
- NVD CVE-2020-6998
Fencer Vulns keeps one entry per vulnerability: the CVE id wins, then GHSA, and records that alias each other are merged, except that two CVEs always keep separate entries. The same data is available as JSON.