CVE-2019-5167 json
An exploitable command injection vulnerability exists in the iocheckd service ‘I/O-Check’ function of the WAGO PFC 200 version 03.02.02(14).
published 2020-03-10 6 y ago modified 2026-06-17 4 mo ago also EUVD-2019-14772
- cvss
- 7.8
- version 3.1, NVD
- cisa kev
- Not listed
- not in CISA's catalog
- epss
- 1.2%
- EPSS 1.2% chance of exploitation in 30 days, percentile 68%
- public exploits
- 0
- none known
Summary
An exploitable command injection vulnerability exists in the iocheckd service ‘I/O-Check’ function of the WAGO PFC 200 version 03.02.02(14). At 0x1e3f0 the extracted dns value from the xml file is used as an argument to /etc/config-tools/edit_dns_server %s dns-server-nr=%d dns-server-name=<contents of dns node> using sprintf(). This command is later executed via a call to system(). This is done in a loop and there is no limit to how many dns entries will be parsed from the xml file.
Exploit prediction
1.21% chance of exploitation in the next 30 days, higher than 68% of all scored CVEs (FIRST EPSS, 2026-11-08).
Exploits and checks
- talosintelligence.com https://talosintelligence.com/vulnerability_reports/TALOS-2019-0962 referenced PoC, tagged "exploit" by a source, unverified
CVSS scores
| assigned by | version | score | vector |
|---|---|---|---|
| NVD | 3.1 | 7.8 | CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H |
| NVD | 2.0 | 7.2 | AV:L/AC:L/Au:N/C:C/I:C/A:C |
Affected products
- Wago WAGO PFC200 Firmware
Classification
- Weakness
-
- CWE-78 Improper Neutralization of Special Elements used in an OS Command
References
-
talosintelligence.com
/vulnerability_reports/TALOS-2019-0962
exploit, third-party-advisory
Sources
- CVE List CVE-2019-5167
- NVD CVE-2019-5167
Fencer Vulns keeps one entry per vulnerability: the CVE id wins, then GHSA, and records that alias each other are merged, except that two CVEs always keep separate entries. The same data is available as JSON.