CVE-2017-6865 json

A vulnerability has been identified in Primary Setup Tool (PST) (All versions < V4.2 HF1), SIMATIC Automation Tool (All versions < V3.0), S…

published 2017-05-11 9 y ago modified 2026-06-17 4 mo ago also EUVD-2017-15919

cvss
6.5
version 3.0, NVD
cisa kev
Not listed
not in CISA's catalog
epss
0.5%
EPSS 0.5% chance of exploitation in 30 days, percentile 40%
public exploits
0
none known

Summary

A vulnerability has been identified in Primary Setup Tool (PST) (All versions < V4.2 HF1), SIMATIC Automation Tool (All versions < V3.0), SIMATIC NET PC-Software (All versions < V14 SP1), SIMATIC PCS 7 V8.1 (All versions), SIMATIC PCS 7 V8.2 (All versions < V8.2 SP1), SIMATIC STEP 7 (TIA Portal) V13 (All versions < V13 SP2), SIMATIC STEP 7 (TIA Portal) V14 (All versions < V14 SP1), SIMATIC STEP 7 V5.X (All versions < V5.6), SIMATIC WinAC RTX 2010 SP2 (All versions), SIMATIC WinAC RTX F 2010 SP2 (All versions), SIMATIC WinCC (TIA Portal) V13 (All versions < V13 SP2), SIMATIC WinCC (TIA Portal) V14 (All versions < V14 SP1), SIMATIC WinCC V7.2 and prior (All versions), SIMATIC WinCC V7.3 (All versions < V7.3 Update 15), SIMATIC WinCC V7.4 (All versions < V7.4 SP1 Upd1), SIMATIC WinCC flexible 2008 (All versions < flexible 2008 SP5), SINAUT ST7CC (All versions installed in conjunction with SIMATIC WinCC < V7.3 Update 15), SINEMA Server (All versions < V14), SINUMERIK 808D Programming Tool (All versions < V4.7 SP4 HF2), SMART PC Access (All versions < V2.3), STEP 7 - Micro/WIN SMART (All versions < V2.3), Security Configuration Tool (SCT) (All versions < V5.0). Specially crafted PROFINET DCP broadcast packets sent to the affected products on a local Ethernet segment (Layer 2) could cause a Denial-of-Service condition of some services. The services require manual restart to recover.

Vendor advisories

What the vendors themselves say about their products: affected, fixed or not affected, and what to do.

cisa ICSA-17-129-01 updated cvss 6.5

ICSA-17-129-01 Siemens devices using the PROFINET Discovery and Configuration Protocol (Update K)

show 12 more

Facts from CISA's republication of the vendor's own advisory (CSAF); the linked advisory is the authoritative source. CISA notification · csaf

Exploit prediction

0.47% chance of exploitation in the next 30 days, higher than 40% of all scored CVEs (FIRST EPSS, 2026-11-08).

CVSS scores

assigned by version score vector
NVD 3.0 6.5 CVSS:3.0/AV:A/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
NVD 2.0 6.1 AV:A/AC:L/Au:N/C:N/I:N/A:C

Affected products

  • Siemens AG Primary Setup Tool (PST)
  • Siemens AG SIMATIC Automation Tool
  • Siemens AG SIMATIC NET PC-Software
  • Siemens AG SIMATIC PCS 7 V8.1
  • Siemens AG SIMATIC PCS 7 V8.2
  • Siemens AG SIMATIC STEP 7 (TIA Portal) V13
  • Siemens AG SIMATIC STEP 7 (TIA Portal) V14
  • Siemens AG SIMATIC STEP 7 V5.X
  • Siemens AG SIMATIC WinAC RTX 2010 SP2
  • Siemens AG SIMATIC WinAC RTX F 2010 SP2
  • Siemens AG SIMATIC WinCC (TIA Portal) V13
  • Siemens AG SIMATIC WinCC (TIA Portal) V14
  • Siemens AG SIMATIC WinCC V7.2 and prior
  • Siemens AG SIMATIC WinCC V7.3
  • Siemens AG SIMATIC WinCC V7.4
  • Siemens AG SIMATIC WinCC flexible 2008
  • Siemens AG SINAUT ST7CC
  • Siemens AG SINEMA Server
  • Siemens AG SINUMERIK 808D Programming Tool
  • Siemens AG SMART PC Access
  • Siemens AG STEP 7 - Micro/WIN SMART
  • Siemens AG Security Configuration Tool (SCT)

Classification

Weakness
  • CWE-20 Improper Input Validation