CVE-2017-6017 json
A Resource Exhaustion issue was discovered in Schneider Electric Modicon M340 PLC BMXNOC0401, BMXNOE0100, BMXNOE0110, BMXNOE0110H, BMXNOR02…
published 2017-06-30 9 y ago modified 2026-06-17 4 mo ago also EUVD-2017-15085
- cvss
- 7.5
- version 3.0, NVD
- cisa kev
- Not listed
- not in CISA's catalog
- epss
- 4.8%
- EPSS 4.8% chance of exploitation in 30 days, percentile 92%
- public exploits
- 0
- none known
Summary
A Resource Exhaustion issue was discovered in Schneider Electric Modicon M340 PLC BMXNOC0401, BMXNOE0100, BMXNOE0110, BMXNOE0110H, BMXNOR0200H, BMXP341000, BMXP342000, BMXP3420102, BMXP3420102CL, BMXP342020, BMXP342020H, BMXP342030, BMXP3420302, BMXP3420302H, and BMXP342030H. A remote attacker could send a specially crafted set of packets to the PLC causing it to freeze, requiring the operator to physically press the reset button on the PLC in order to recover.
Vendor advisories
What the vendors themselves say about their products: affected, fixed or not affected, and what to do.
cisa ICSA-17-054-03 updated cvss 7.5
Schneider Electric Modicon M340 PLC (Update A)
-
Schneider Electric Software, LLC M1E CPUs Schneider Electric Software, LLC M340 CPUs with firmware < 2.9 Schneider Electric Software, LLC M580 CPUs with firmware < 2.3 Schneider Electric Software, LLC Premium CPUs Schneider Electric Software, LLC Quantum CPUs with firmware < 3.52affected: mitigation “M340: https://www.schneider-electric.fr/fr/search/V2.9?filters=CAT_PRD_DOC_FIRMUPD” schneider-electric.fr
From CISA ICS and IT advisories (CSAF, https://github.com/cisagov/CSAF), a U.S. Government work; changed: reduced to products, statuses and remediations. CISA notification · csaf
Exploit prediction
4.81% chance of exploitation in the next 30 days, higher than 92% of all scored CVEs (FIRST EPSS, 2026-11-08).
CVSS scores
| assigned by | version | score | vector |
|---|---|---|---|
| NVD | 3.0 | 7.5 | CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H |
| NVD | 2.0 | 7.8 | AV:N/AC:L/Au:N/C:N/I:N/A:C |
Affected products
- n/a Schneider Electric Modicon M340 PLC
Classification
- Weakness
-
- CWE-400 Uncontrolled Resource Consumption
References
- schneider-electric.com /en/download/document/SEVD-2017-048-02/
-
securityfocus.com
/bid/96414
vdb-entry, third-party-advisory
-
ics-cert.us-cert.gov
/advisories/ICSA-17-054-03
mitigation, third-party-advisory, us-government-resource
Sources
- CVE List CVE-2017-6017
- NVD CVE-2017-6017
Fencer Vulns keeps one entry per vulnerability: the CVE id wins, then GHSA, and records that alias each other are merged, except that two CVEs always keep separate entries. The same data is available as JSON.