CVE-2017-13997 json
A Missing Authentication for Critical Function issue was discovered in Schneider Electric InduSoft Web Studio v8.0 SP2 or prior, and InTouc…
published 2017-10-02 9 y ago modified 2026-06-17 4 mo ago also EUVD-2017-5512
- cvss
- 9.8
- version 3.0, NVD
- cisa kev
- Not listed
- not in CISA's catalog
- epss
- 5.1%
- EPSS 5.1% chance of exploitation in 30 days, percentile 92%
- public exploits
- 0
- none known
Summary
A Missing Authentication for Critical Function issue was discovered in Schneider Electric InduSoft Web Studio v8.0 SP2 or prior, and InTouch Machine Edition v8.0 SP2 or prior. InduSoft Web Studio provides the capability for an HMI client to trigger script execution on the server for the purposes of performing customized calculations or actions. A remote malicious entity could bypass the server authentication and trigger the execution of an arbitrary command. The command is executed under high privileges and could lead to a complete compromise of the server.
Vendor advisories
What the vendors themselves say about their products: affected, fixed or not affected, and what to do.
cisa ICSA-17-264-01 updated cvss 9.8
Schneider Electric InduSoft Web Studio, InTouch Machine Edition
-
Schneider Electric Software, LLC InduSoft Web Studio < 8.0 SP2 Schneider Electric Software, LLC InTouch Machine Edition < 8.0 SP2affected: vendor fix, mitigation “Schneider Electric recommends users using InduSoft Web Studio v8.0 SP2 or prior should upgrade and apply InduSoft Web Studio v8.0 SP2 Patch 1 as soon as possible.” gcsresource.invensys.com
From CISA ICS and IT advisories (CSAF, https://github.com/cisagov/CSAF), a U.S. Government work; changed: reduced to products, statuses and remediations. CISA notification · csaf
Exploit prediction
5.05% chance of exploitation in the next 30 days, higher than 92% of all scored CVEs (FIRST EPSS, 2026-11-08).
CVSS scores
| assigned by | version | score | vector |
|---|---|---|---|
| NVD | 3.0 | 9.8 | CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H |
| NVD | 2.0 | 10.0 | AV:N/AC:L/Au:N/C:C/I:C/A:C |
Affected products
- n/a Schneider Electric InduSoft Web Studio, InTouch Machine Edition
Classification
- Weakness
-
- CWE-306 Missing Authentication for Critical Functionality
References
-
ics-cert.us-cert.gov
/advisories/ICSA-17-264-01
mitigation, third-party-advisory, us-government-resource
-
securityfocus.com
/bid/100952
vdb-entry, third-party-advisory
Sources
- CVE List CVE-2017-13997
- NVD CVE-2017-13997
Fencer Vulns keeps one entry per vulnerability: the CVE id wins, then GHSA, and records that alias each other are merged, except that two CVEs always keep separate entries. The same data is available as JSON.