Skip to content
Fencer Vulns
high 7.5

CVE-2016-7113 json

A vulnerability has been identified in Firmware variant PROFINET IO for EN100 Ethernet module : All versions < V1.04.01; Firmware variant M…

published 2016-09-06 10 y ago modified 2026-06-17 4 mo ago also EUVD-2016-7992

cvss
7.5
version 3.0, NVD
cisa kev
Not listed
not in CISA's catalog
epss
3.0%
EPSS 3.0% chance of exploitation in 30 days, percentile 87%
public exploits
0
none known

Summary

A vulnerability has been identified in Firmware variant PROFINET IO for EN100 Ethernet module : All versions < V1.04.01; Firmware variant Modbus TCP for EN100 Ethernet module : All versions < V1.11.00; Firmware variant DNP3 TCP for EN100 Ethernet module : All versions < V1.03; Firmware variant IEC 104 for EN100 Ethernet module : All versions < V1.21; EN100 Ethernet module included in SIPROTEC Merging Unit 6MU80 : All versions < 1.02.02. Specially crafted packets sent to port 80/tcp could cause the affected device to go into defect mode.

Vendor advisories

What the vendors themselves say about their products: affected, fixed or not affected, and what to do.

cisa ICSA-16-250-01 updated cvss 5.3

Siemens SIPROTEC 4 and SIPROTEC Compact Vulnerabilities

  • Siemens EN100 Ethernet module (as optional for SIPROTEC 4 and SIPROTEC Compact) <V4.29
    affected: mitigation “Siemens provides firmware update V4.29 for EN100 modules included in SIPROTEC 4 and SIPROTEC Compact devices to fix the vulnerabilities. Siemens recommends users update to the latest firmware version.”

From CISA ICS and IT advisories (CSAF, https://github.com/cisagov/CSAF), a U.S. Government work; changed: reduced to products, statuses and remediations. CISA notification · csaf

cisa ICSA-17-187-03F updated cvss 5.3

ICSA-17-187-03F Siemens SIPROTEC 4 and SIPROTEC Compact (Update F)

  • Siemens EN100 Ethernet module included in SIPROTEC Merging Unit 6MU80 <1.02.02
    affected: mitigation siemens.com
  • Siemens Firmware variant DNP3 TCP for EN100 Ethernet module <V1.03 Siemens Firmware variant IEC 104 for EN100 Ethernet module <V1.21 Siemens Firmware variant Modbus TCP for EN100 Ethernet module <V1.11.00 Siemens Firmware variant PROFINET IO for EN100 Ethernet module <V1.04.01
    affected: vendor fix, mitigation support.industry.siemens.com
  • Siemens SIPROTEC 7SD686 <V_4.03, <V_4.05 Siemens SIPROTEC 7SJ66 <V_4.20, <V_4.30 Siemens SIPROTEC 7SJ686 <V_4.83, <V_4.87 Siemens SIPROTEC 7UT686 <V_4.01, <V_4.02
    affected: mitigation siemens.com

Facts from CISA's republication of the vendor's own advisory (CSAF); the linked advisory is the authoritative source. CISA notification · csaf

cisa ICSA-17-334-01 updated cvss 5.3

Siemens SWT3000

  • Siemens IEC 61850 firmware < 4.29.01 Siemens TPOP firmware < 01.01.00
    affected: vendor fix siemens.com

From CISA ICS and IT advisories (CSAF, https://github.com/cisagov/CSAF), a U.S. Government work; changed: reduced to products, statuses and remediations. CISA notification · csaf

cisa ICSA-17-187-02 updated cvss 7.5

Siemens Reyrolle

  • Siemens EN100 Ethernet modules as optional for Reyrolle < 4.29.01
    affected: vendor fix

From CISA ICS and IT advisories (CSAF, https://github.com/cisagov/CSAF), a U.S. Government work; changed: reduced to products, statuses and remediations. CISA notification · csaf

Exploit prediction

3.00% chance of exploitation in the next 30 days, higher than 87% of all scored CVEs (FIRST EPSS, 2026-11-08).

CVSS scores

assigned by version score vector
NVD 3.0 7.5 CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
NVD 2.0 7.8 AV:N/AC:L/Au:N/C:N/I:N/A:C

Classification

Weakness
  • CWE-399 Resource Management Errors

References

Sources

Fencer Vulns keeps one entry per vulnerability: the CVE id wins, then GHSA, and records that alias each other are merged, except that two CVEs always keep separate entries. The same data is available as JSON.