CVE-2016-7112 json
A vulnerability has been identified in Firmware variant PROFINET IO for EN100 Ethernet module : All versions < V1.04.01; Firmware variant M…
published 2016-09-06 10 y ago modified 2026-06-17 4 mo ago also EUVD-2016-7991
- cvss
- 9.8
- version 3.0, NVD
- cisa kev
- Not listed
- not in CISA's catalog
- epss
- 2.9%
- EPSS 2.9% chance of exploitation in 30 days, percentile 86%
- public exploits
- 0
- none known
Summary
A vulnerability has been identified in Firmware variant PROFINET IO for EN100 Ethernet module : All versions < V1.04.01; Firmware variant Modbus TCP for EN100 Ethernet module : All versions < V1.11.00; Firmware variant DNP3 TCP for EN100 Ethernet module : All versions < V1.03; Firmware variant IEC 104 for EN100 Ethernet module : All versions < V1.21; EN100 Ethernet module included in SIPROTEC Merging Unit 6MU80 : All versions < 1.02.02. Attackers with network access to the device's web interface (port 80/tcp) could possibly circumvent authentication and perform certain administrative operations.
Vendor advisories
What the vendors themselves say about their products: affected, fixed or not affected, and what to do.
cisa ICSA-16-250-01 updated cvss 5.3
Siemens SIPROTEC 4 and SIPROTEC Compact Vulnerabilities
-
Siemens EN100 Ethernet module (as optional for SIPROTEC 4 and SIPROTEC Compact) <V4.29affected: mitigation “Siemens provides firmware update V4.29 for EN100 modules included in SIPROTEC 4 and SIPROTEC Compact devices to fix the vulnerabilities. Siemens recommends users update to the latest firmware version.”
From CISA ICS and IT advisories (CSAF, https://github.com/cisagov/CSAF), a U.S. Government work; changed: reduced to products, statuses and remediations. CISA notification · csaf
cisa ICSA-17-187-03F updated cvss 5.3
ICSA-17-187-03F Siemens SIPROTEC 4 and SIPROTEC Compact (Update F)
-
Siemens EN100 Ethernet module included in SIPROTEC Merging Unit 6MU80 <1.02.02affected: mitigation siemens.com
-
Siemens Firmware variant DNP3 TCP for EN100 Ethernet module <V1.03 Siemens Firmware variant IEC 104 for EN100 Ethernet module <V1.21 Siemens Firmware variant Modbus TCP for EN100 Ethernet module <V1.11.00 Siemens Firmware variant PROFINET IO for EN100 Ethernet module <V1.04.01affected: vendor fix, mitigation support.industry.siemens.com
-
Siemens SIPROTEC 7SD686 <V_4.03, <V_4.05 Siemens SIPROTEC 7SJ66 <V_4.20, <V_4.30 Siemens SIPROTEC 7SJ686 <V_4.83, <V_4.87 Siemens SIPROTEC 7UT686 <V_4.01, <V_4.02affected: mitigation siemens.com
Facts from CISA's republication of the vendor's own advisory (CSAF); the linked advisory is the authoritative source. CISA notification · csaf
cisa ICSA-17-334-01 updated cvss 5.3
Siemens SWT3000
-
Siemens IEC 61850 firmware < 4.29.01 Siemens TPOP firmware < 01.01.00affected: vendor fix siemens.com
From CISA ICS and IT advisories (CSAF, https://github.com/cisagov/CSAF), a U.S. Government work; changed: reduced to products, statuses and remediations. CISA notification · csaf
cisa ICSA-17-187-02 updated cvss 5.3
Siemens Reyrolle
-
Siemens EN100 Ethernet modules as optional for Reyrolle < 4.29.01affected: vendor fix
From CISA ICS and IT advisories (CSAF, https://github.com/cisagov/CSAF), a U.S. Government work; changed: reduced to products, statuses and remediations. CISA notification · csaf
Exploit prediction
2.86% chance of exploitation in the next 30 days, higher than 86% of all scored CVEs (FIRST EPSS, 2026-11-08).
CVSS scores
| assigned by | version | score | vector |
|---|---|---|---|
| NVD | 3.0 | 9.8 | CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H |
| NVD | 2.0 | 10.0 | AV:N/AC:L/Au:N/C:C/I:C/A:C |
Classification
- Weakness
-
- CWE-287 Improper Authentication
References
Sources
- CVE List CVE-2016-7112
- NVD CVE-2016-7112
Fencer Vulns keeps one entry per vulnerability: the CVE id wins, then GHSA, and records that alias each other are merged, except that two CVEs always keep separate entries. The same data is available as JSON.